Description
Description
The BITE 2 and BITE 2P receiver stores the readings in its internal memory. These measurements, along with other maintenance data such as ambient and pilot cell temperatures and ac ripple current, assist in determining the overall condition of battery systems. Megger recommends that impedance measurements with the BITE 2 or BITE 2P be made part of a battery maintenance program with readings taken and recorded semiannually for flooded batteries and quarterly for VRLA.
Unlike load cycle testing that involves substantial downtime and repeated discharges, using the instruments require no battery discharge, nor do they stress the battery in any way compared to other techniques. With a test time of less than 20 seconds for each cell and intercell connector, one person can easily, quickly, and precisely measure internal cell impedance, dc terminal voltage and intercell connection resistance without taking the battery system off line.
Key Features
- Determines condition of lead-acid and NiCd cells up to 7000 Ah
- On-board Pass/Warning/Fail indications
- Robust, repeatable instruments
- On-line testing
NIST-Traceable Calibrations
Standard Calibration Price (without data): Request a Quote
ANSI Z540 Calibration Price (with as-found & as-left data): Request a Quote
ISO/IEC 17025:2005 Accredited Calibration Price (with data & uncertainties): Request a Quote
ANSI Z540.3 with data & uncertainties and Guardbanding: Request a Quote
Test & Measurement Equipment Repair Services: Request a Quote